Air Heater — Condensate Load
The steam demand, condensate load and trap capacity of a steam-to-air coil.
Unit system
Inputs
Steam demand = condensate load
217.4kg/h
Heat duty
130.7kW
Details
| Trap capacity (with safety factor) | 434.8 kg/h |
| Air mass flow | 12,690 kg/h |
| Inlet air density | 1.269 kg/m³ |
| Volume flow at outlet | 11,258 m³/h |
| Steam temperature | 133.5 °C |
| Assessment | Inlet air is above freezing; a standard coil arrangement is adequate. |
Assumptions
- Only SENSIBLE heat is involved: air being heated does not condense its moisture, and the dew point is unchanged.
- Air is treated as an ideal gas. At atmospheric and low pressures the deviation is a fraction of a per cent.
Continue with this result
Calculation report
A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.
Source
- Enerji dengesi · Q = ṁ_hava·cp·ΔT ÷ verim; ṁ_buhar = Q ÷ h_fg
- İdeal gaz denklemi · ρ = p ÷ (R·T), R_hava = 287,05 J/(kg·K)
- IAPWS-IF97 (R7-97) · Doyma sıcaklığı ve gizli ısı · 2007
Results are for engineering pre-assessment and are not a product selection commitment. Final responsibility rests with the user.