Continuous Flow Heating — Condensate Load
The steam demand and trap capacity for heating a liquid flowing continuously through an exchanger.
Inputs
Steam demand = condensate load
2,417kg/h
Heat duty
1,432kW
Details
| Trap capacity (with safety factor) | 3,625 kg/h |
| Steam temperature | 143.6 °C |
| Latent heat | 2,133 kJ/kg |
| Steam-to-outlet approach | 63.61 K |
| Assessment | The temperature difference is workable; size the trap on the full-load capacity. |
Assumptions
- Only the LATENT heat of the steam is used. Condensate leaves at saturation; sub-cooling reduces the steam demand slightly.
- Specific heat is taken as constant; over a wide range enter a mean value.
Continue with this result
Calculation report
A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.
Source
- Enerji dengesi · Q = ṁ·cp·ΔT ÷ verim; ṁ_buhar = Q ÷ h_fg
- IAPWS-IF97 (R7-97) · Doyma sıcaklığı ve gizli ısı · 2007