Batch Tank Heating — Condensate Load
The steam needed to bring a tank batch up to temperature — heat-up and hold loads given separately.
Inputs
Heat-up load
640.7kg/h
Holding load
6.075kg/h
Details
| Trap capacity (with safety factor) | 961.1 kg/h |
| Heat-up duty | 379.7 kW |
| Total energy per batch | 379.7 kWh |
| Surface loss at target | 3.6 kW |
| Steam temperature | 143.6 °C |
| Selection note | The heat-up load is several times the hold load — size the coil and trap on HEAT-UP, or the target is never reached. |
Assumptions
- The surface loss is taken to rise linearly during heat-up, so its mean is half the loss at target.
- Agitator power and the tank metal itself are neglected; for heavy-walled tanks add the metal mass to the batch.
Continue with this result
Calculation report
A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.
Source
- Enerji dengesi · Q = m·cp·ΔT ÷ süre + U·A·ΔT; ṁ_buhar = Q ÷ h_fg
- IAPWS-IF97 (R7-97) · Doyma sıcaklığı ve gizli ısı · 2007
Results are for engineering pre-assessment and are not a product selection commitment. Final responsibility rests with the user.