Condensate Line Sizing — Two-Phase Flow

Pipe size for a trap discharge, a common return header or a pumped line — with the flash steam counted in.

Unit system

Inputs

Selected size

DN 80 (3")

Flash fraction (by mass)

0.1523

Details

Inside diameter of the selected pipe77.92 mm
Minimum required inside diameter77.52 mm
Vapour velocity in the selected size14.85 m/s
Volume flow of the flash steam254.9 m³/h
Volume flow of the condensate0.8845 m³/h
Vapour share of the volume0.9965
If sized on the liquid aloneDN 15 — 5.3× smaller
Warning99.7 % of the volume is vapour. This is not a WATER line; sized on the water flow it chokes and back-pressures the trap.

Assumptions

  • The condensate is taken as SATURATED water ahead of the trap. Sub-cooled condensate flashes less and the line gets smaller.
  • The size follows the vapour velocity; the water is carried as a film along the bottom and is assumed to take no cross-section.
  • On long runs the pressure drop must be checked separately — this screen applies the velocity criterion only.

Continue with this result

Calculation report

A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.

Source

  • Enerji dengesi · flash oranı = (h′_yüksek − h′_alçak) ÷ h_fg,alçak
  • IAPWS-IF97 (R7-97) · Doyma entalpileri ve özgül hacimler · 2007
  • ASME B36.10M · Boru iç çapları · 2022