All calculations

Flash Steam Generation

The flash steam formed when condensate drops to a lower pressure, its fraction and the volume increase.

Unit system

Inputs

Flash steam

152.3kg/h

Flash fraction

0.1523

Details

Condensate remaining847.7 kg/h
Power carried by the flash steam95.47 kW
Volume flow of the flash steam254.9 m³/h
Volume flow of the condensate0.8845 m³/h
Volume multiplier289.1
Effect on the lineThe volume grows by tens of times — size the line for the flash steam, not the condensate

Assumptions

  • The condensate is taken as SATURATED water at the upstream pressure. Sub-cooled condensate flashes less, or not at all.
  • The process is adiabatic; line heat loss reduces the flash fraction somewhat.

Continue with this result

Calculation report

A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.

Source

  • Enerji dengesi · flash oranı = (h′_yüksek − h′_alçak) ÷ h_fg,alçak
  • IAPWS-IF97 (R7-97) · Doyma entalpileri ve özgül hacimler · 2007

Results are for engineering pre-assessment and are not a product selection commitment. Final responsibility rests with the user.