Deaerator Steam Consumption
The steam spent bringing feedwater to deaerator temperature, and its share of the boiler load.
Inputs
Deaerator steam use
911.7kg/h
Share of feedwater
0.0887
Details
| Deaerator temperature | 111.4 °C |
| Vented | 30.82 kg/h |
| Heating duty | 615.9 kW |
| Makeup plus condensate inflow | 9,393 kg/h |
Assumptions
- Mixing is taken as adiabatic; the vessel’s surface loss is not included (small on an insulated deaerator).
- This steam never reaches the process. Boiler capacity must cover production PLUS the deaerator’s own use.
Calculation report
A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.
Source
- Enerji dengesi · W·h_buhar + (F−W)·h_giriş = F·h_çıkış + vent
- IAPWS-IF97 (R7-97) · Entalpiler · 2007
Results are for engineering pre-assessment and are not a product selection commitment. Final responsibility rests with the user.