Steam Main — Start-up and Running Load
The condensate capacity needed to warm a cold steam main, and the running load once it is up to temperature.
Inputs
Start-up load
163.1kg/h
Running load
10.34kg/h
Details
| Trap capacity (with safety factor) | 326.3 kg/h |
| Start-up ÷ running | 15.8 |
| Metal mass heated (kg) | 1,849 |
| Steam temperature | 179.9 °C |
| Start-up duty | 91.28 kW |
| Heat loss per metre | 0.05788 kW |
| Selection note | The start-up load is many times the running load — sizing the trap on RUNNING duty floods the line and causes water hammer. |
Assumptions
- A mean specific heat of 490 J/(kg·K) is used for the metal (carbon steel, 20–200 °C).
- The running load is for a line fully at steam temperature; during warm-up the loss is smaller.
- Condensate is assumed drained evenly along the line. Long mains need drain points every 30–50 m.
Continue with this result
Calculation report
A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.
Source
- Enerji dengesi · Q = m·cp·ΔT ÷ süre; ṁ_buhar = Q ÷ h_fg
- EN ISO 12241 · Boru yüzeyinden ısı kaybı ve yüzey sıcaklığı · 2022
- ASME B36.10M · Boru dış çapı ve et kalınlığı · 2022
- IAPWS-IF97 (R7-97) · Doyma sıcaklığı ve gizli ısı · 2007
Results are for engineering pre-assessment and are not a product selection commitment. Final responsibility rests with the user.