All calculations

Blowdown Heat Recovery

The steam recovered by flashing the blowdown, the heat recovered in the exchanger, and what is left.

Unit system

Inputs

Flash steam recovered

36.39kg/h

Total heat recovered

42.26kW

Details

Flash fraction0.1328
Power in the flash steam22.5 kW
Power taken in the exchanger19.76 kW
Water going to drain237.6 kg/h
Recovery ratio0.7937

Assumptions

  • The flash fraction is the excess of the boiler-pressure saturated-liquid enthalpy over the flash-pressure one, divided by the latent heat.
  • The flash steam is assumed to be USABLE in the deaerator. If it is not, only the exchanger term counts.

Calculation report

A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.

Source

  • Enerji dengesi · Flash oranı ve eşanjör yükü
  • IAPWS-IF97 (R7-97) · Doymuş sıvı ve buhar entalpileri · 2007

Results are for engineering pre-assessment and are not a product selection commitment. Final responsibility rests with the user.