The water dropping out after the compressor and aftercooler, the dew point, and the cooler’s latent load.
Inputs
Condensate formed
7.28kg/h
Water per day (litres)
174.7
Details
| Pressure dew point at outlet | 35 °C |
| Dew point at intake | 19.15 °C |
| Intake humidity ratio (kg/kg dry air) | 0.01392 |
| Outlet humidity ratio | 0.00441 |
| Latent load on the aftercooler | 5.057 kW |
| Water per year (m³) | 44 |
Assumptions
- The air is taken as SATURATED at the aftercooler outlet. With a dryer the dew point falls further and condensation continues there.
- Air is an ideal gas; the water vapour partial pressure comes from the IAPWS-IF97 saturation curve.
Calculation report
A PDF carrying the inputs, results, assumptions and the source. A one-time code is sent to your address.
Source
- Psikrometri · W = 0,621945 · p_buhar ÷ (p − p_buhar)
- IAPWS-IF97 (R7-97) · Su buharı doyma basıncı · 2007